Vaillant aroTHERM F.731 fault code
Vaillant aroTHERM heat pumps
What the Vaillant aroTHERM F.731 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The refrigerant high-pressure switch has tripped.
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
Likely causes
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p58.
- Refrigerant pressure too high. The integrated high-pressure switch in the outdoor unit has tripped at 41.5 bar (g) or 42.5 bar (abs)
- Insufficient energy output via the condenser
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
What Vaillant says to do
- Purging the building circuit
- Too low a volume flow as a result of closing single room controls in an underfloor heating system
- Check that the dirt filter that is in place is permeable
- Refrigerant flow rate too low (e.g. electronic expansion valve defective, 4-port diverter valve is mechanically blocked, filter is blocked). Inform customer service.
- Cooling mode: Check the fan unit for dirt
- Check the high-pressure switch and high-pressure sensor
- Reset the high-pressure switch and carry out a manual reset on the product.
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p58.
UK models this code applies to
Tap yours to open F.731 on that machine.
Now the harder half: proving what caused it
F.731 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.731 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.582Electronic expansion valve fault
- F.585Condenser outlet temperature sensor fault
- F.718Fan unit 1 blocked
- F.723Building circuit: pressure too low
- F.729Compressor outlet temperature too low
- F.732Compressor outlet temperature too high
- F.733Evaporation temperature too low
- F.734Condensation temperature too low
- F.735Evaporation temperature too high
- F.737Condensation temperature too high