Vaillant aroTHERM F.582 fault code
Vaillant aroTHERM heat pumps
What the Vaillant aroTHERM F.582 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The EEV is not responding correctly.
Safety: Safe isolation before disconnecting the EEV coil.
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
Likely causes
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p57.
- EEV is not connected correctly or there is a cable break to the coil
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
What Vaillant says to do
- Check the plug connections and, if required, replace the coil from the EEV
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p57.
UK models this code applies to
Tap yours to open F.582 on that machine.
F.582 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.582 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.582 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.517Compressor outlet temperature sensor
- F.519Building circuit return temperature sensor
- F.520Building circuit flow temperature sensor
- F.526EEV outlet temperature sensor fault
- F.546High-pressure sensor fault
- F.585Condenser outlet temperature sensor fault
- F.718Fan unit 1 blocked
- F.723Building circuit: pressure too low
- F.729Compressor outlet temperature too low
- F.731High-pressure switch open