Vaillant aroTHERM F.732 fault code
Vaillant aroTHERM heat pumps
What the Vaillant aroTHERM F.732 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Discharge (compressor-outlet, TT135) temperature has exceeded 130 °C — application limits exceeded, the EEV not opening correctly, or the refrigerant charge too low (frequent defrost).
Safety: Read the refrigerant off the outdoor unit's data plate first. aroTHERM split is R410A (A1, not flammable); aroTHERM plus is R290 (A3, flammable): on R290, no ignition sources and ventilate before any refrigerant-side work. Leak-check with a detector rated for the refrigerant on the plate.
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
Likely causes
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p58.
- The compressor outlet temperature is above 130 °C:
- Application limits exceeded
- EEV does not work or does not open correctly
- Refrigerant volume too low (frequent defrosting due to extremely low evaporation temperatures)
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
What Vaillant says to do
- Check the compressor inlet sensor and outlet sensor
- Check the compressor outlet temperature sensor (TT135)
- Check the EEV (does the EEV move to the limit stop? Use the sensor/actuator test)
- Check the refrigerant volume (see Technical data)
- Carry out a leak-tightness test
- Check whether the service valves on the outdoor unit are open.
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p58.
UK models this code applies to
Tap yours to open F.732 on that machine.
Now the harder half: proving what caused it
F.732 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.732 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.585Condenser outlet temperature sensor fault
- F.718Fan unit 1 blocked
- F.723Building circuit: pressure too low
- F.729Compressor outlet temperature too low
- F.731High-pressure switch open
- F.733Evaporation temperature too low
- F.734Condensation temperature too low
- F.735Evaporation temperature too high
- F.737Condensation temperature too high
- F.741Building-circuit return temperature too low (during de-icing)