What it means

Inverter overcurrent shutdown, power factor correction filter (PFC)

Inverter overcurrent shutdown, power factor correction filter (PFC). Refrigerant circuit off: Inverter and compressor cannot be switched on.

Safety: Safe isolation, then TREAT THE DC LINK AS LIVE. The electrolytic capacitors hold a lethal charge after the supply is off. Discharge through a suitable resistor across the + and − terminals and confirm with a meter on DC before touching the board. Never short the terminals with a screwdriver.

Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)

Needs double checking. This answer looks right, but the maker's book does not print it for this exact model. Check it against the unit's own book.

Likely causes

Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p151.

Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)

What Viessmann says to do

  1. Check air inlet of outdoor unit for obstruction and check fan can rotate freely.
  2. Check electrical terminal area of outdoor unit for dirt.
  3. Check VCMU refrigerant circuit controller power supply.
  4. Isolate the system from the power supply. Wait at least 2 min. Switch on the system.
  5. Check all connections to the compressor: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Replace cable if necessary.
  6. Check phase connections for compressor for clockwise rotating field.
  7. Replace inverter.

Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p151.

UK models this code applies to

Tap yours to open F.843 on that machine.

Now the harder half: proving what caused it

F.843 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.

Chase F.843 on your machine →

Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.

Or watch one get chased — free demo →Prove the cause: guided investigation →

The first steps are free to try, no account. Your first full investigation is free with one.

One full investigation is free with a free account.

Download on the App Store

Or use it in your browser on any phone or laptop.

Related codes

All Viessmann Vitocal fault codes →