Viessmann Vitocal F.864 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.864 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p153.
- Defrost process aborted 10 times Further message: A.143
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Acknowledge messages.
- If necessary, isolate system from power supply. Wait at least 2 min. Switch on the system.
- Check minimum flow rate of secondary circuit.
- Flush the system if necessary. Vent via the venting program.
- Check all installed heating filters on the secondary side. Clean the following filters if necessary: Ball valve with filter in the outdoor unit · Heating filter with magnetite separation, e.g. in the return lines on the secondary side before the inlet to the outdoor unit and before the inlet to the indoor unit · Heating filter in heat meter · Further filters
- Check parameters for circulation pumps.
- Check the installation location and installation conditions of the outdoor unit: Ambient temperature too high, e.g. due to solar radiation · Air short circuit, intake of dirt · Minimum clearances, e.g. for installation in a recess · Susceptibility to wind · Obstacles, modification, coverings · Minimum clearances · Position of air inlet temperature sensor: Avoid draughts.
- Check the evaporator for dirt. If necessary, clean evaporator. If necessary, carefully de-ice the evaporator mechanically.
- Check that the condensate can drain freely. Clean the condensate drain if necessary.
- Check the electric ribbon heater (if installed): Fan ring heater · Electric ribbon heater for condensate pan · Ribbon heater for condensate drain
- Check oil sump heater.
- Check instantaneous heating water heater. If required, replace the instantaneous heating water heater.
- Run the software update.
- Check the float air vent valve.
- Inform the manufacturer's technical support.
- Unlock refrigerant circuit.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p153.
UK models this code applies to
F.864 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.864 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.864 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.843Inverter overcurrent shutdown, power factor correction filter (PFC)
- F.845Unsuitable / mis-programmed inverter
- F.846Compressor rotating field counter-rotating
- F.847Inverter current sensor recognises unchanging compressor current
- F.848Inverter current sensor recognises fluctuating compressor current
- F.865High-pressure fault (air / shut circuit / blocked pumps / dirty…
- F.866Low-pressure fault (low refrigerant / dirty evaporator / fans blocked…
- F.867Float air-vent valve responded — air in circuit / faulty air-vent /…
- F.876Lead break, flow sensor
- F.881Refrigerant-circuit safety shutdown