Viessmann Vitocal F.845 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.845 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Safety: Safe isolation before disconnecting the compressor or testing the inverter board — capacitors hold charge.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p152.
- Wrong inverter installed or inverter configured incorrectly
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Check which inverter is being used.
- Isolate the system from the power supply. Wait at least 2 min. Switch on the system.
- Check software version of the VCMU refrigerant circuit controller via ViGuide. Run software update if required.
- Replace inverter.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p152.
UK models this code applies to
F.845 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.845 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.845 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.837Power supply on compressor faulty
- F.838Inverter control faulty
- F.839Compressor blocked
- F.841Compressor running unevenly (excess torque / high power draw)
- F.843Inverter overcurrent shutdown, power factor correction filter (PFC)
- F.846Compressor rotating field counter-rotating
- F.847Inverter current sensor recognises unchanging compressor current
- F.848Inverter current sensor recognises fluctuating compressor current
- F.864Defrost attempt unsuccessful
- F.865High-pressure fault (air / shut circuit / blocked pumps / dirty…