Viessmann Vitocal F.834 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.834 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Inverter phase fault on mains side. Refrigerant circuit off: Inverter and compressor cannot be switched on.
Safety: Safe isolation, then TREAT THE DC LINK AS LIVE. The electrolytic capacitors hold a lethal charge after the supply is off. Discharge through a suitable resistor across the + and − terminals and confirm with a meter on DC before touching the board. Never short the terminals with a screwdriver.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p148.
- Power supply on inverter faulty
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Check the surge protection device in the meter box or on the outdoor unit. Switch on if necessary.
- Check all connections to the inverter: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Replace cable if necessary.
- Check the phase connections on the inverter for a clockwise rotating field.
- Check whether there is a fault in the power grid caused by the power supply utility.
- Only Vitocal 250-A.../252-A, sizes 16 to 19: Check the fuses on plug X6 on the inverter (IPE). Replace inverter if necessary.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p148.
UK models this code applies to
Tap yours to open F.834 on that machine.
Now the harder half: proving what caused it
F.834 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.834 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.829Flow too low — outdoor-unit ball-valve filter contaminated
- F.830Fault, inverter current sensor
- F.831Fault, current sensor, power factor correction filter (PFC) inverter
- F.832Inverter temperature sensor faulty
- F.833Fault, temperature sensor, power factor correction filter (PFC)…
- F.835Unsuitable / mis-programmed inverter
- F.836Load current of inverter too high (excess current)
- F.837Power supply on compressor faulty
- F.838Inverter control faulty
- F.839Compressor blocked