Viessmann Vitocal F.830 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.830 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Fault, inverter current sensor. Refrigerant circuit off: Inverter and compressor cannot be switched on.
Safety: Safe isolation before disconnecting the compressor or testing the inverter board — capacitors hold charge.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p147.
- Measuring error, inverter current sensor
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Isolate the system from the power supply. Wait at least 2 min. Switch on the system.
- Check all connections to the compressor: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Replace cable if necessary.
- Check phase connections for compressor for clockwise rotating field.
- Replace inverter.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p147.
UK models this code applies to
Tap yours to open F.830 on that machine.
Now the harder half: proving what caused it
F.830 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.830 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.820Lead break, EEV2
- F.823Short circuit, EEV1
- F.824Short circuit, EEV2
- F.827High-limit safety cut-out responded on instantaneous heater
- F.829Flow too low — outdoor-unit ball-valve filter contaminated
- F.831Fault, current sensor, power factor correction filter (PFC) inverter
- F.832Inverter temperature sensor faulty
- F.833Fault, temperature sensor, power factor correction filter (PFC)…
- F.834Inverter phase fault on mains side
- F.835Unsuitable / mis-programmed inverter