Viessmann Vitocal F.801 fault code

Viessmann Vitocal heat pumps

What the Viessmann Vitocal F.801 fault code means, from the manufacturer's own service literature, and the UK models it applies to.

What it means

4-way diverter valve faulty, no circuit reversal

Safety: Safe isolation before testing the valve coil — live mains present.

Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)

Likely causes

Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p146.

Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)

What Viessmann says to do

  1. Check refrigerant used.
  2. Check 4-way diverter valve: 230 V~ power supply at X1 on VCMU refrigerant circuit controller · Voltage L1 at X3.1 for relay 2 · Voltage L1 at X3.2 with relay 2 switched. If required, replace VCMU refrigerant circuit controller. · Isolate the system from the power supply. Check resistor R on disconnected coil of 4-way diverter valve. If R > 300 kΩ, replace the 4-way diverter valve. · Remove and flush the 4-way diverter valve. Clean connecting lines. If required, replace the 4-way diverter valve.
  3. Check high pressure sensor connecting lead, connections and plug-in connection X20.1 to X20.3 on EHCU electronics module. Replace high pressure sensor if required.
  4. Replace the VCMU refrigerant circuit controller.
  5. Unlock refrigerant circuit.

Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p146.

UK models this code applies to

F.801 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.

Now the harder half: proving what caused it

F.801 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.

Chase F.801 on your machine →

Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.

Or watch one get chased — free demo →Prove the cause: guided investigation →

The first steps are free to try, no account. Your first full investigation is free with one.

One full investigation is free with a free account.

Download on the App Store

Or use it in your browser on any phone or laptop.

Related codes

All Viessmann Vitocal fault codes →