Viessmann Vitocal F.797 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.797 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p144.
- Mechanical fault on secondary pump/heating circuit pump, heating/cooling circuit 1, e.g. impeller blocked
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- At the centre of the pump casing, press the coupling and simultaneously turn the pump shaft.
- Check the impeller. If required, remove the rotor. Remove dirt. If required, flush and vent the system.
- Start actuator test and function check via HMI programming unit or ViGuide. Check function of the circulation pump.
- Other pump noises: Gurgling: Vent system again. · Hissing, or circulation pump getting hot: Check set pump rate. Adjust if required. · Knocking or rattling: Replace the circulation pump.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p144.
UK models this code applies to
F.797 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.797 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.797 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.788Fault, control/supply of 4/3-way valve
- F.7904/3-way valve motor mis-mounted or valve faulty
- F.791Phase L1 missing on instantaneous heating water heater
- F.792Phase L2 missing on instantaneous heating water heater
- F.793Phase L3 missing on instantaneous heating water heater
- F.798HC2 pump faulty
- F.799Secondary/HC1 pump faulty
- F.800HC2 pump faulty
- F.8014-way diverter valve faulty, no circuit reversal
- F.808Lower fan not running