Vaillant aroTHERM F.752 fault code
Vaillant aroTHERM heat pumps
What the Vaillant aroTHERM F.752 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Escalated from S.575: an internal electronics fault on the outdoor unit's inverter PCB, or mains voltage outside 70-282 V. After three occurrences F.752 is displayed.
Safety: Safe isolation, then TREAT THE DC LINK AS LIVE. The electrolytic capacitors hold a lethal charge after the supply is off. Discharge through a suitable resistor across the + and − terminals and confirm with a meter on DC before touching the board. Never short the terminals with a screwdriver.
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
Likely causes
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p59.
- Internal electronics fault on the inverter PCB
- Mains voltage outside of 70 V–282 V
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
What Vaillant says to do
- Check the integrity of the power supply cables and compressor connection cables. The plugs must audibly click into place.
- Check the cable
- Check the mains voltage. The mains voltage must be between 195 V and 253 V.
- Check the phases
- Replace the frequency converter, if required
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p59.
UK models this code applies to
Tap yours to open F.752 on that machine.
F.752 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.752 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.752 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.733Evaporation temperature too low
- F.734Condensation temperature too low
- F.735Evaporation temperature too high
- F.737Condensation temperature too high
- F.741Building-circuit return temperature too low (during de-icing)
- F.753Connection fault: frequency converter not recognised
- F.7554-port valve position incorrect
- F.774Air inlet temperature sensor
- F.785Fan unit 2 blocked
- F.788Building circuit pump fault