Vaillant aroTHERM F.1100 fault code
Vaillant aroTHERM heat pumps
What the Vaillant aroTHERM F.1100 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The immersion heater's safety cut-out (overheat stat) has operated.
Safety: Safe isolation before working on the immersion heater or its wiring.
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
Likely causes
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p61.
- The safety cut-out on the electric back-up heater is open due to:
- Insufficient volume flow or air in the building circuit
- The immersion heater is operated when the building circuit is not filled
- Immersion heater operation at flow temperatures above 95 °C trips the safety fuse of the safety cut-out and requires that the fuse be replaced
- Feed-in of external heat into the building circuit
Source: Vaillant hydraulic station installation & maintenance instructions 0020257319 (VWL 57…127/5 IS), fault-message table
What Vaillant says to do
- Check the circulation in the building circuit pump
- If required, open the stopcocks
- Replace the safety cut-out
- Reduce or stop the external heat that is entering
- Check that the dirt filter that is in place is permeable
Causes and remedies as printed in Vaillant 0020257319_05 (hydraulic station VWL 57…127/5 IS), Appendix I Fault codes, PDF p61.
UK models this code applies to
Tap yours to open F.1100 on that machine.
F.1100 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.1100 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.1100 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.785Fan unit 2 blocked
- F.788Building circuit pump fault
- F.817Frequency converter fault: compressor
- F.818Frequency converter: mains voltage fault
- F.819Frequency converter fault: overheating
- F.820Connection fault: building circuit pump
- F.821Immersion heater flow sensor fault
- F.825Condenser inlet temperature sensor fault
- F.1117Compressor phase failure
- F.1120Heating rod: phase failure