Mitsubishi Ecodan P8 fault code
Mitsubishi Ecodan heat pumps
What the Mitsubishi Ecodan P8 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Detected from pipe-temperature relationships (manual: TH6–THW2 ≤ 1 °C / TH7–TH3 ≤ 1 °C at ≥ 61 Hz) — refrigerant not doing what the mode demands.
Safety: Read the refrigerant off the outdoor unit's data plate first. R32 (A2L) and R290 (A3) are flammable: ventilate and remove ignition sources first. R410A (A1) is not flammable. Leak-check with equipment rated for the refrigerant on the plate.
How to read it — ftc controller: Ecodan check codes show on the FTC / main controller display. (Ecodan service manual OCH727, §9-2 self-diagnosis action table)
Source: Ecodan service manual OCH727 §9-2
Likely causes
- Gas leak / low charge
- Stop valve part-closed
- 4-way valve not switched
- Thermistor disconnected
Source: Ecodan service manual OCH727 §9-2
UK models this code applies to
Tap yours to open P8 on that machine.
P8 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Outdoor units38
Now the harder half: proving what caused it
P8 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase P8 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- L9Low primary flow detected by flow sensor
- LDBoiler flow/return thermistor (THWB1/THWB2) open/short
- P1Room temperature thermistor (TH1A/TH1B) open/short
- P2Liquid refrigerant thermistor (TH2) open/short
- P6Plate heat-exchanger freeze protection
- U1High pressure (high-pressure switch 63H operated)
- U2Abnormal high discharge temperature
- U3Discharge thermistor (TH4) open/short
- U4Outdoor thermistor open/short
- U8Outdoor fan motor abnormality