Mitsubishi Ecodan P2 fault code
Mitsubishi Ecodan heat pumps
What the Mitsubishi Ecodan P2 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Open ≤ −39 °C, short ≥ 88.5 °C. Not raised during defrost or for 10 minutes after — retest outside that window before condemning.
Safety: Safe isolation before disconnecting sensors or working on the PCB.
How to read it — ftc controller: Ecodan check codes show on the FTC / main controller display. (Ecodan service manual OCH727, §9-2 self-diagnosis action table)
Source: Ecodan FTC service manual §10-4 self-diagnosis and action + §10-6 checking component parts' function (pump curves, recommended water flow range, thermistor tables)
Likely causes
- Loose or corroded connector
- Faulty thermistor
- PCB fault
Source: Ecodan FTC service manual §10-4 self-diagnosis and action + §10-6 checking component parts' function (pump curves, recommended water flow range, thermistor tables)
UK models this code applies to
Tap yours to open P2 on that machine.
Outdoor units44
Now the harder half: proving what caused it
P2 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase P2 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- L6Circulation water freeze protection
- L8Heating operation error (no temperature rise)
- L9Low primary flow detected by flow sensor
- LDBoiler flow/return thermistor (THWB1/THWB2) open/short
- P1Room temperature thermistor (TH1A/TH1B) open/short
- P6Plate heat-exchanger freeze protection
- P8Refrigerant circuit abnormality
- U1High pressure (high-pressure switch 63H operated)
- U2Abnormal high discharge temperature
- U3Discharge thermistor (TH4) open/short