Mitsubishi Ecodan U1 fault code

Mitsubishi Ecodan heat pumps

What the Mitsubishi Ecodan U1 fault code means, from the manufacturer's own service literature, and the UK models it applies to.

What it means

High pressure (high-pressure switch 63H operated)

The outdoor unit's high-pressure switch (63H) operated while the compressor was running. Mitsubishi prints the trip point as 4.15 MPa for the PUZ-WM range and 3.2 MPa for the PUZ-WZ range (OCH816 / OCH880). The check code on the controller is U1 (4-digit code 1302).

How to read it — ftc controller: Ecodan check codes show on the FTC / main controller display. (Ecodan service manual OCH727, §9-2 self-diagnosis action table)

Source: Ecodan OCH727A service manual (PUZ-WM) §9-2 self-diagnosis action table p25, render-checked 11 Nov 2026; PUZ-WZ50-80 OCH816 p34 and PUZ-WZ85-140 OCH880 p38; files under.

Likely causes

Source: Ecodan OCH727A service manual (PUZ-WM) §9-2 self-diagnosis action table p25, render-checked 11 Nov 2026; PUZ-WZ50-80 OCH816 p34 and PUZ-WZ85-140 OCH880 p38; files under.

UK models this code applies to

U1 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.

Now the harder half: proving what caused it

U1 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.

Chase U1 on your machine →

Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.

Or watch one get chased — free demo →Prove the cause: guided investigation →

The first steps are free to try, no account. Your first full investigation is free with one.

One full investigation is free with a free account.

Download on the App Store

Or use it in your browser on any phone or laptop.

Related codes

All Mitsubishi Ecodan fault codes →