What it means
The manual's wording: cooling-heating switching error. The system cannot change over between modes — the 4-way valve isn't reaching its position, or the unit can't confirm that it has.
Safety: Safe isolation before testing the 4-way-valve coil — 230 V present at the coil.
How to read it — remote self-diagnosis, with beeps: Hold the remote's self-diagnosis button about 5 seconds until the code segment blinks, then press repeatedly to step through codes. A LONG CONTINUOUS beep from the indoor unit marks the stored code — a short or double beep means not this one. (Daikin CTXM/FTXM-M operation manual 3PEN393186-10J, remote self-diagnosis)
Source: Daikin CTXM/FTXM-M operation manual 3PEN393186-10J, malfunction-code table (remote self-diagnosis)
Likely causes
- Reversing (4-way) valve coil open or not energised
- Valve stuck mid-position
- Coil thermistor mis-reading, so the unit thinks it hasn't changed over
- Outdoor PCB drive fault
Source: Daikin CTXM/FTXM-M operation manual 3PEN393186-10J, malfunction-code table (remote self-diagnosis)
UK models this code applies to
Tap yours to open EA on that machine.
Wall-mounted31
Cassettes48
Ducted32
Ceiling suspended13
Ceiling or floor1
Floor consoles9
Floor-standing10
Indoor and outdoor pairs24
Multi-split outdoor units8
Outdoor units179
EA on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Wall-mounted164
Ceiling suspended8
Ceiling or floor2
Floor consoles8
Indoor and outdoor pairs1
Outdoor units27
Other models69
Now the harder half: proving what caused it
EA names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase EA on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- C9Room / suction air thermistor fault
- E1Outdoor unit PCB fault
- E5Compressor motor overload / overheat
- E6Compressor start failure / lock
- E7Outdoor fan motor fault
- F3Abnormal discharge pipe temperature
- F6Abnormal high pressure / refrigerant overcharge
- H0Sensor fault (compressor system)
- H6Compressor position-detection sensor error
- H8Compressor input current (CT) system fault