Viessmann Vitocal F.998 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.998 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Communication error, refrigerant circuit controller to EHCU/flow rate signal. Only for heat pumps with integral flow sensor: Refrigerant circuit temporarily off.
Safety: Safe isolation before opening terminal covers — mains present on the interconnect.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p175.
- The VCMU refrigerant circuit controller is not receiving a signal from the flow sensor of the indoor unit.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
Only for heat pumps with integral flow sensor:
- If message F.876 is also present: Check flow sensor and connections X19.1 to X19.4 on the EHCU electronics module: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
- If message F.876 is also present: Check voltage U between X19.2 and X19.4 on the EHCU electronics module: U = 5 V : Replace flow sensor. · No voltage: Replace the EHCU electronics module.
- Replace the EHCU electronics module.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p175.
UK models this code applies to
Tap yours to open F.998 on that machine.
Now the harder half: proving what caused it
F.998 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.998 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.993Lead break, ext. heating-water/coolant buffer sensor
- F.994Short circuit, ext. heating-water buffer sensor
- F.995Lead break, ext. heating-water buffer sensor
- F.996Short circuit, ext. coolant buffer sensor
- F.997Lead break, ext. coolant buffer sensor
- F.1009Oil-sump heater fault
- F.1010Secondary-circuit pressure sensor fault
- F.1011High-pressure sensor fault
- F.1012Low-pressure sensor fault
- F.1045External heat generator not ready