All fault codes

Viessmann Vitocal F.998 fault code

Viessmann Vitocal heat pumps

What the Viessmann Vitocal F.998 fault code means, from the manufacturer's own service literature, and the UK models it applies to.

What it means

Communication error, refrigerant circuit controller to EHCU/flow rate signal

Communication error, refrigerant circuit controller to EHCU/flow rate signal. Only for heat pumps with integral flow sensor: Refrigerant circuit temporarily off.

Safety: Safe isolation before opening terminal covers — mains present on the interconnect.

Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)

Needs double checking. This answer looks right, but the maker's book does not print it for this exact model. Check it against the unit's own book.

Likely causes

Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p175.

Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)

What Viessmann says to do

Only for heat pumps with integral flow sensor:

  1. If message F.876 is also present: Check flow sensor and connections X19.1 to X19.4 on the EHCU electronics module: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  2. If message F.876 is also present: Check voltage U between X19.2 and X19.4 on the EHCU electronics module: U = 5 V : Replace flow sensor. · No voltage: Replace the EHCU electronics module.
  3. Replace the EHCU electronics module.

Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p175.

UK models this code applies to

Tap yours to open F.998 on that machine.

Now the harder half: proving what caused it

F.998 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.

Chase F.998 on your machine →

Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.

Or watch one get chased — free demo →Prove the cause: guided investigation →