Viessmann Vitocal F.1009 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.1009 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p177.
- Fault, oil sump heater
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Check 6.3 A fuse on the VCMU refrigerant circuit controller. Replace fuse if necessary.
- Check the function of the relay at X4.1/X4.2 on the VCMU refrigerant circuit controller. If necessary, replace VCMU refrigerant circuit controller.
- Check the oil sump heater connections at X4.1 to X4.2 on the VCMU refrigerant circuit controller: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
- Check resistor R on the disconnected plug X4.1/X4.2. If R < 1.256 kΩ or R > 1.388 kΩ, replace oil sump heater.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p177.
UK models this code applies to
F.1009 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.1009 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.1009 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.994Short circuit, ext. heating-water buffer sensor
- F.995Lead break, ext. heating-water buffer sensor
- F.996Short circuit, ext. coolant buffer sensor
- F.997Lead break, ext. coolant buffer sensor
- F.998Communication error, refrigerant circuit controller to EHCU/flow rate…
- F.1010Secondary-circuit pressure sensor fault
- F.1011High-pressure sensor fault
- F.1012Low-pressure sensor fault
- F.1045External heat generator not ready
- F.10493/2-way mixing valve not switching (ext. heat gen.)