Viessmann Vitocal F.1011 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.1011 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The high-pressure sensor fault sensor reads open or short circuit.
Safety: Safe isolation before disconnecting sensors or working on the PCB.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p178.
- Fault, high pressure sensor · Further messages: A.82, A.93
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Check the high pressure sensor and connections X14.1 to X14.3 on the VCMU refrigerant circuit controller: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
- Check voltage between X14.2/X14.3 in system operation. If it deviates from the curve, replace the high pressure sensor.
- Replace VCMU refrigerant circuit controller.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p178.
UK models this code applies to
F.1011 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.1011 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.1011 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.996Short circuit, ext. coolant buffer sensor
- F.997Lead break, ext. coolant buffer sensor
- F.998Communication error, refrigerant circuit controller to EHCU/flow rate…
- F.1009Oil-sump heater fault
- F.1010Secondary-circuit pressure sensor fault
- F.1012Low-pressure sensor fault
- F.1045External heat generator not ready
- F.10493/2-way mixing valve not switching (ext. heat gen.)
- F.1050Short circuit, boiler-water temp ext. heat generator
- F.1051Lead break, boiler-water temp ext. heat generator