Viessmann Vitocal F.992 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.992 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The ext. heating-water/coolant buffer sensor sensor reads open or short circuit.
Safety: Safe isolation before disconnecting sensors or working on the PCB.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann One Base service instructions 6194799 (3/2022), Vitocal 150-A/151-A and 250-A/252-A, p65.
- Short circuit, temperature sensor of external heating water/coolant buffer cylinder
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Check the settings in the commissioning assistant. Adjust settings if required.
- Check resistance value (NTC 10 kΩ) at connection X17 of the EHCU electronics module. Replace sensor if necessary.
Causes and measures as printed in Viessmann One Base service instructions 6194799 (3/2022), Vitocal 150-A/151-A and 250-A/252-A, p65.
UK models this code applies to
F.992 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.992 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.992 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.983Internal inverter fault
- F.984Control of EEV1 faulty
- F.985Control of EEV2 faulty
- F.990Short circuit, secondary-circuit temp sensor
- F.991Lead break, secondary-circuit temp sensor
- F.993Lead break, ext. heating-water/coolant buffer sensor
- F.994Short circuit, ext. heating-water buffer sensor
- F.995Lead break, ext. heating-water buffer sensor
- F.996Short circuit, ext. coolant buffer sensor
- F.997Lead break, ext. coolant buffer sensor