Viessmann Vitocal F.984 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.984 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p171.
- Stator of expansion valve 1 faulty · Expansion valve 1 blocked in "open" position · Expansion valve 1 clogged
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Check connections X8.1 to X8.5 on the VCMU refrigerant circuit controller: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Replace cable if necessary.
- Isolate the system from the power supply. Wait at least 2 min. Switch on the system.
- Check electronic expansion valve 1 via actuator test.
- Check resistor R for 20 °C at the disconnected plug of electronic expansion valve 1: On all 4 coils of the stator between pin 5 and pin 1 to 4 in each case: If R < 43 Ω or > 49 Ω, replace stator.
- Replace the VCMU refrigerant circuit controller.
- Check mechanism of electronic expansion valve 1: Expansion valve 1 is open and blocked: Suction gas pressure too high · Expansion valve 1 clogged: Suction gas pressure too low · Expansion valve 1 sticks: Suction gas pressure fluctuates.
- Replace electronic expansion valve 1.
- Unlock refrigerant circuit.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p171.
UK models this code applies to
F.984 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.984 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.984 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.876Lead break, flow sensor
- F.881Refrigerant-circuit safety shutdown
- F.912Interior temp sensor fault
- F.913Interior (inverter) temperature too high
- F.983Internal inverter fault
- F.985Control of EEV2 faulty
- F.990Short circuit, secondary-circuit temp sensor
- F.991Lead break, secondary-circuit temp sensor
- F.992Short circuit, ext. heating-water/coolant buffer sensor
- F.993Lead break, ext. heating-water/coolant buffer sensor