Viessmann Vitocal F.87 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.87 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p124.
- Hydraulic system pressure too high
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Reduce system pressure to the permissible level. If message returns after approx. 10 s, drain the system. Fill again and vent.
- Check the water pressure sensor and connection X11 on the EHCU electronics module: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
- Replace cable.
- Replace water pressure sensor.
- Replace EHCU electronics module.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p124.
UK models this code applies to
F.87 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.87 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.87 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.14Short circuit, outside temp (0°C substitute used)
- F.33Lead break, air-inlet temp
- F.34Short circuit, air-inlet temp
- F.74Hydraulic system pressure too low
- F.75No flow in secondary circuit or flow sensor faulty
- F.91DIO electronics-module comms error
- F.92ADIO electronics-module comms error
- F.93M2IO electronics-module comms error
- F.94SDIO electronics-module comms error
- F.99PlusBus comms error (modules unavailable)