Viessmann Vitocal F.75 fault code

Viessmann Vitocal heat pumps

What the Viessmann Vitocal F.75 fault code means, from the manufacturer's own service literature, and the UK models it applies to.

What it means

No flow in secondary circuit or flow sensor faulty

Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)

Likely causes

Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p123.

Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)

What Viessmann says to do

  1. If this message appears after commissioning, check the float air vent valve. Restart the filling function.
  2. Open shut-off valves in direction of flow. Remove any blockages. If necessary, heat the pipe to the non-return valve/ball valve with filter to thaw frozen residual heating water.
  3. Check the float air vent valve. Check for refrigerant leaks (R290). Carry out the venting program. Replace the float air vent valve if necessary.
  4. Clean the heating water filter. Clean the dirt separator if required.
  5. Check connection of flow sensor (if installed) at X19.1 to X19.4 on the EHCU electronics module: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
  6. Check voltage U between X19.2 and X19.4 in EHCU electronics module: If U = 5 V, replace the flow sensor (if installed). · No voltage: Replace EHCU electronics module.
  7. Check circulation pump: If status indicator is red: Check power supply fuse. · Check connections X6.1 to X6.3 (230 V~) and X7.1 to X7.3 (PWM signal) on the EHCU electronics module: – Check wires and plugs for correct seating. – Check connections for contact corrosion. – Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. Replace connecting cable if necessary. · Check the impeller. If required, remove the rotor. Remove dirt. If required, flush the system. · Other pump noises: Replace the circulation pump.

Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p123.

UK models this code applies to

F.75 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.

Now the harder half: proving what caused it

F.75 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.

Chase F.75 on your machine →

Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.

Or watch one get chased — free demo →Prove the cause: guided investigation →

The first steps are free to try, no account. Your first full investigation is free with one.

One full investigation is free with a free account.

Download on the App Store

Or use it in your browser on any phone or laptop.

Related codes

All Viessmann Vitocal fault codes →