Viessmann Vitocal F.548 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.548 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The flow temp hc4 with mixer sensor reads open or short circuit.
Safety: Safe isolation before disconnecting sensors or working on the PCB.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p135.
- Lead break, flow temperature sensor, heating/cooling circuit 4 with mixer · Incorrect configuration during commissioning
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Check configuration. Adjust settings if required.
- Check setting of rotary switch S1 on ADIO electronics module (EM-MX extension): See chapter "Rotary switch S1 on electronics modules".
- Check connection TS1.1/TS1.2 on the ADIO electronics module: Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage.
- Check resistor R for NTC 10 kΩ on the disconnected plug. If R > 300 kΩ, replace the sensor.
- Replace the ADIO electronics module.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p135.
UK models this code applies to
F.548 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.548 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.548 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.543Short circuit, flow temp HC1 with mixer
- F.544Lead break, flow temp HC2 with mixer
- F.545Short circuit, flow temp HC2 with mixer
- F.546Lead break, flow temp HC3 with mixer
- F.547Short circuit, flow temp HC3 with mixer
- F.549Short circuit, flow temp HC4 with mixer
- F.623Lead break, return temp (mixer HC1)
- F.624Short circuit, return temp (mixer HC1)
- F.625Lead break, return temp HC2
- F.626Short circuit, return temp HC2