Mitsubishi Ecodan L3 fault code
Mitsubishi Ecodan heat pumps
What the Mitsubishi Ecodan L3 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
THW1 or THW2 reads ≥80 °C for 10 consecutive seconds. Nearly always a water-flow problem, not a sensor problem. On the FTC, LP stands for the Legionella prevention mode: this code can be raised while that mode is running (OCH571A p.42 key).
How to read it — ftc controller: Ecodan check codes show on the FTC / main controller display. (Ecodan service manual OCH727, §9-2 self-diagnosis action table)
Source: Ecodan FTC service manual §10-4 self-diagnosis and action + §10-6 checking component parts' function (pump curves, recommended water flow range, thermistor tables)
Likely causes
- Low primary flow (pump / strainer / air / leak)
- Valve fault (2-way or 3-way)
- Booster-heater relay stuck (BHC1/BHC2/BHCP)
- THW1/THW2 fault
- FTC board
Source: Ecodan FTC service manual §10-4 self-diagnosis and action + §10-6 checking component parts' function (pump curves, recommended water flow range, thermistor tables)
UK models this code applies to
Tap yours to open L3 on that machine.
Outdoor units44
Now the harder half: proving what caused it
L3 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase L3 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- E4Main controller communication failure (FTC receives nothing)
- E5FTC transmission failure
- E6Indoor/outdoor communication failure (reception)
- E8Indoor ↔ outdoor unit communication error
- F5High-pressure switch (63H) operated
- L4DHW tank overheat protection (THW5 ≥75 °C)
- L5Water-circuit thermistor (THW1/2/5/6/7/8/9) open/short
- L6Circulation water freeze protection
- L8Heating operation error (no temperature rise)
- L9Low primary flow detected by flow sensor