Mitsubishi Ecodan L5 fault code
Mitsubishi Ecodan heat pumps
What the Mitsubishi Ecodan L5 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Any water-circuit thermistor open (≤ −39 °C) or short (≥ 88.5 °C). Request code 567 in Running information names the exact sensor.
Safety: Safe isolation before disconnecting sensors or working on the PCB.
How to read it — ftc controller: Ecodan check codes show on the FTC / main controller display. (Ecodan service manual OCH727, §9-2 self-diagnosis action table)
Source: Ecodan FTC service manual §10-4 self-diagnosis and action + §10-6 checking component parts' function (pump curves, recommended water flow range, thermistor tables)
Likely causes
- Loose or corroded connector
- Faulty thermistor
- PCB fault
Source: Ecodan FTC service manual §10-4 self-diagnosis and action + §10-6 checking component parts' function (pump curves, recommended water flow range, thermistor tables)
UK models this code applies to
Tap yours to open L5 on that machine.
Outdoor units44
Now the harder half: proving what caused it
L5 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase L5 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- E6Indoor/outdoor communication failure (reception)
- E8Indoor ↔ outdoor unit communication error
- F5High-pressure switch (63H) operated
- L3Circulation water overheat protection (≥80 °C)
- L4DHW tank overheat protection (THW5 ≥75 °C)
- L6Circulation water freeze protection
- L8Heating operation error (no temperature rise)
- L9Low primary flow detected by flow sensor
- LDBoiler flow/return thermistor (THWB1/THWB2) open/short
- P1Room temperature thermistor (TH1A/TH1B) open/short