Viessmann Vitocal F.430 fault code
Viessmann Vitocal heat pumps
What the Viessmann Vitocal F.430 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Safety: Safe isolation before opening terminal covers — mains present on the interconnect.
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
Likely causes
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p131.
- Gateway (WAGO KNX/TP) communication error
Source: Viessmann One Base service instructions 6194799 (2022), fault & warning tables (Vitocal 150-A/151-A)
What Viessmann says to do
- Check system configuration for gateway: CAN bus subscriber number 90
- Turn off the ON/OFF switch on the indoor unit. Wait at least 2 min. Turn on the ON/OFF switch.
- Check the CAN bus connections: Connections X8.1 to X8.3 on plug 91 on the HPMU electronics module · Wall mounted indoor unit: Connection on device underside, 6-pole connection socket on the left, terminals 1.CAN L to
- CAN H Floorstanding indoor unit: Terminal area for extra low voltage (ELV) < 42 V, luster terminal for bus connections, terminals
- CAN L to 91.CAN H Check wires and plugs for correct seating. · Check connections for contact corrosion. · Check cables for mechanical damage, e.g. crushing, kinking, chafing or breakage. · Check CAN L/CAN H assignment. · CAN Ground (GND) must not be connected. · Check cable type: Li2YCYv, twisted pair, shielded or 2-core CAT5, shielded · Check cable length. · Check the position and number of terminators.
- Replace CAN bus Gateway cable.
- Check power supply to the gateway.
- Replace gateway.
Causes and measures as printed in Viessmann Service instructions Diagnosis 6199893 (2026-01), Vitocal 150-A/151-A/250-A/252-A, p131.
UK models this code applies to
F.430 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
F.430 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase F.430 on your machine →Free, no sign-up. We don't hold a chart for this code yet — pick the model for its manual section.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- F.152Short circuit, hot-gas temp
- F.155Fault, electronic expansion valve 1
- F.156Fault, electronic expansion valve 2
- F.160CAN-bus general comms fault between modules
- F.425Time sync not possible
- F.431KNX/TP gateway comms error
- F.454Wrong operating-software version across modules (HPMU/EHCU/VCMU)
- F.472Energy-meter comms error
- F.519BACnet/IP gateway comms error
- F.520Modbus comms error inverter↔VCMU