LG Therma V CH23 fault code
LG Therma V heat pumps
What the LG Therma V CH23 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
Safety: Safe isolation, then TREAT THE DC LINK AS LIVE. The electrolytic capacitors hold a lethal charge after the supply is off. Discharge through a suitable resistor across the + and − terminals and confirm with a meter on DC before touching the board. Never short the terminals with a screwdriver.
Source: LG AWHP Service Manual MFL68682007 (© 2020, R32 Therma V) — error codes + component tables; scope: code SET & fan figure whole-range, compressor winding confirmed 12/14/16 kW, thermistor tables part-level
Likely causes
- Supply dip, surge or poor neutral
- Undersized or poorly terminated supply cable (volt drop on start)
- Lost phase / unbalanced supply (3-phase models)
- Rectifier, PFC or DC-link fault on the inverter board
Source: LG AWHP Service Manual MFL68682007 (© 2020, R32 Therma V) — error codes + component tables; scope: code SET & fan figure whole-range, compressor winding confirmed 12/14/16 kW, thermistor tables part-level
UK models this code applies to
Tap yours to open CH23 on that machine.
Hydro units and cylinders1
Outdoor units36
Now the harder half: proving what caused it
CH23 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase CH23 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- CH18Electric backup-heater outlet sensor open/short
- CH19Electric backup-heater outlet sensor open/short (printed as CH18's…
- CH20Electric heater overheated (thermal cut-out / fuse blown)
- CH21DC peak / IPM fault (compressor stopped on power-module Fault-Out)
- CH22CT current error (outdoor over-current)
- CH24High-pressure error (discharge pressure excessive)
- CH26No-position error (compressor initial start abnormal)
- CH27PFC over-current
- CH29Compressor over-current (inverter input over limit)
- CH32Discharge-pipe temperature high