Refrigerant Converter

Pressure ↔ tempWhat replaces it

The gas on the plate → what is documented to go in instead, and whether that means the same machine or a new one. Every line says where it comes from; nothing is from memory.

On the plate

R404A · A1 · GWP 3922

GWP ≥ 2,500. Under retained Regulation (EU) 517/2014 Art. 13(3), VIRGIN R404A may not be used to service or maintain equipment with a charge of 40 t CO₂e or more (≈10.2 kg of R404A) since 1 Jan 2020; recycled/reclaimed R404A permitted for that until 1 Jan 2030. Below 40 t CO₂e the service ban does not apply, but the gas is expensive and scarce.

Retrofit — same machine, after recovery, drier and oil per the guide

A retrofit is still: recover and weigh, change the drier, follow the retrofit guide on oil and seals, charge by weight, relabel the machine, record it. Never a top-up of a different gas. Glides are approximate — the blend's own P-T data is what this app's tables use for superheat (dew) and subcooling (bubble).

The guide: “replacement refrigerant” — three different things