Refrigerant charge limit and minimum room size

How much refrigerant a room can take, or how big the room must be for your charge.

Biggest charge for this room
3.25kg R32
0 kg7.98 kg · EN 378-1
Work out
Where the indoor unit sits
Floor area of the room (m²)Length × width, off your tape measure

On a multi-split, check the smallest room with an indoor unit in it, against the whole system's charge.

This is a guide. The manufacturer's installation manual comes first: some ask for more room than this, and many print their own minimum floor area table. Use theirs.

How this is worked out (EN 378-1)

Worked out: 2.5 × 0.307^1.25 × 1.8 × √10.00 = 3.25 kg; 0.75 × 0.307 × 1.8 × 10.00 = 4.14 kg; the smaller one counts

Where these numbers come from