LG air conditioning CH62 fault code
LG air conditioning
What the LG air conditioning CH62 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The outdoor inverter heat-sink has exceeded ~85°C. This is a thermal condition — not a sensor open/short (that is CH65).
Safety: Isolate before working on the inverter board — capacitors hold charge and the heat-sink runs hot.
Source: LG Universal Split self-diagnosis table (LG Electronics Australia + Orion/Macedo LG A/C fault-code sheets); cross-checked vs LG US support error-code guide
Likely causes
- Debris blocking the heat-sink fins
- Poor contact between the inverter module and heat-sink (loose / dry of thermal paste)
- High ambient / poor airflow around the outdoor unit
- Faulty heat-sink thermistor (fault code CH65 has the test — enter it in the code box above)
Source: LG Universal Split self-diagnosis table (LG Electronics Australia + Orion/Macedo LG A/C fault-code sheets); cross-checked vs LG US support error-code guide
UK models this code applies to
Tap yours to open CH62 on that machine.
Wall-mounted58
Cassettes25
Ducted23
Ceiling suspended12
Floor-standing1
Multi-split outdoor units3
CH62 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
CH62 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase CH62 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- CH26Inverter compressor start / position failure
- CH29Inverter compressor over-current (>30A)
- CH32Compressor discharge temperature high (>105°C)
- CH41Compressor discharge sensor fault
- CH44Outdoor air sensor fault
- CH45Condenser coil sensor fault
- CH46Compressor suction sensor fault
- CH61Condenser coil high temperature (>65°C)
- CH65Inverter heat-sink sensor fault
- CH67Outdoor fan motor fault