LG air conditioning CH29 fault code
LG air conditioning
What the LG air conditioning CH29 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The inverter compressor input current exceeds ~30A — the compressor is overloaded.
Safety: Safe isolation before disconnecting the compressor or testing the inverter board.
Source: LG Universal Split self-diagnosis table (LG Electronics Australia + Orion/Macedo LG A/C fault-code sheets); cross-checked vs LG US support error-code guide
Likely causes
- High head pressure (dirty condenser / weak fan / overcharge)
- Restriction or part-closed valve
- EEV underfeeding
- Compressor winding fault
- Low supply voltage
Source: LG Universal Split self-diagnosis table (LG Electronics Australia + Orion/Macedo LG A/C fault-code sheets); cross-checked vs LG US support error-code guide
UK models this code applies to
Tap yours to open CH29 on that machine.
Wall-mounted58
Cassettes25
Ducted23
Ceiling suspended12
Floor-standing1
Multi-split outdoor units3
CH29 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Now the harder half: proving what caused it
CH29 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase CH29 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- CH21Inverter DC peak / IPM over-current
- CH22Compressor over-current (CT)
- CH23Inverter DC-link low voltage (<140V)
- CH24Low/high pressure switch tripped
- CH26Inverter compressor start / position failure
- CH32Compressor discharge temperature high (>105°C)
- CH41Compressor discharge sensor fault
- CH44Outdoor air sensor fault
- CH45Condenser coil sensor fault
- CH46Compressor suction sensor fault