LG air conditioning CH24 fault code
LG air conditioning
What the LG air conditioning CH24 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
A pressure switch has opened. LG latches CH24 only after the switch trips ~5 times within an hour — the low-pressure switch opens at roughly 0.5–1 bar suction, the high-pressure switch at roughly 35–41 bar (exact thresholds vary by model).
Safety: The circuit may be under abnormal pressure — gauge up carefully and let the compressor stop before working on it.
Source: LG Universal Split self-diagnosis table (LG Electronics Australia + Orion/Macedo LG A/C fault-code sheets); cross-checked vs LG US support error-code guide
Likely causes
- Undercharge / leak (low-pressure trip)
- Blocked condenser or failed outdoor fan (high-pressure trip)
- Stop valve part-closed
- Restriction (blocked drier / EEV)
- Faulty pressure switch or missing CN_Press link
Source: LG Universal Split self-diagnosis table (LG Electronics Australia + Orion/Macedo LG A/C fault-code sheets); cross-checked vs LG US support error-code guide
UK models this code applies to
Tap yours to open CH24 on that machine.
Wall-mounted58
Cassettes25
Ducted23
Ceiling suspended12
Floor-standing1
Multi-split outdoor units8
Outdoor units12
Now the harder half: proving what caused it
CH24 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase CH24 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- CH05Indoor/outdoor communication fault
- CH10Indoor fan motor fault
- CH21Inverter DC peak / IPM over-current
- CH22Compressor over-current (CT)
- CH23Inverter DC-link low voltage (<140V)
- CH26Inverter compressor start / position failure
- CH29Inverter compressor over-current (>30A)
- CH32Compressor discharge temperature high (>105°C)
- CH41Compressor discharge sensor fault
- CH44Outdoor air sensor fault