Daikin EA-00 fault code
Daikin Altherma heat pumps
What the Daikin EA-00 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The unit could not complete a changeover between heating and cooling — the reversing valve did not do what it was told.
How to read it — controller display: Altherma error codes show directly on the user interface / main controller display — no button dance needed. (Daikin Altherma 3 M installer reference guide, §14.4.2 error-code table)
Source: Daikin Altherma 3 M installer reference guide 4P685228-1B §14.4.2
Likely causes
- Reversing valve coil open or short
- Valve stuck mid-position
- Insufficient pressure differential to shift the valve
- Low charge
Source: Daikin Altherma 3 M installer reference guide 4P685228-1B §14.4.2
UK models this code applies to
Tap yours to open EA-00 on that machine.
Outdoor units57
EA-00 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Outdoor units44
Now the harder half: proving what caused it
EA-00 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase EA-00 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- E5-00OU: Overheat of inverter compressor motor
- E6-00OU: Compressor startup defect
- E7-00OU: Malfunction of outdoor unit fan motor
- E8-00OU: Power input overvoltage
- E9-00Malfunction of electronic expansion valve
- EC-00Abnormal increase tank temperature
- EC-04Tank preheating
- F3-00OU: Malfunction of discharge pipe temperature
- F6-00OU: Abnormal high pressure in cooling
- FA-00OU: Abnormal high pressure, actuation of HPS