Daikin A1-00 fault code
Daikin Altherma heat pumps
What the Daikin A1-00 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The board has lost the mains zero-crossing reference it times from. Check the supply itself before the board.
Safety: Safe isolation, then TREAT THE DC LINK AS LIVE. The electrolytic capacitors hold a lethal charge after the supply is off. Discharge through a suitable resistor across the + and − terminals and confirm with a meter on DC before touching the board. Never short the terminals with a screwdriver.
How to read it — controller display: Altherma error codes show directly on the user interface / main controller display — no button dance needed. (Daikin Altherma 3 M installer reference guide, §14.4.2 error-code table)
Source: Daikin Altherma 3 M installer reference guide 4P685228-1B §14.4.2
Likely causes
- Loose, corroded or water-damaged connector on the board
- Supply fault or poor neutral presenting as a board error
- Water ingress / corrosion (outdoor boards)
- Main PCB (zero-cross detection) memory or hardware fault
Source: Daikin Altherma 3 M installer reference guide 4P685228-1B §14.4.2
UK models this code applies to
Tap yours to open A1-00 on that machine.
Outdoor units45
A1-00 on these comes from each model's own manual, which may not match the meaning above — tap yours to read it.
Outdoor units56
Now the harder half: proving what caused it
A1-00 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase A1-00 on your machine →Free, no sign-up. Pick the model: where we hold a chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- 89-01Heat exchanger freeze-up protection activated during defrost (error)
- 89-02Heat exchanger freeze-up protection (warning)
- 89-03Heat exchanger freeze-up protection activated during defrost (warning)
- 89-05Heat exchanger freeze-up protection activated during cooling…
- 89-06Heat exchanger freeze-up protection activated during cooling…
- A5-00OU: High pressure peak cut / freeze protection problem
- AA-01Backup heater overheated or BUH power cable not connected
- AC-00Booster heater overheated
- AH-00Tank disinfection not completed correctly
- AJ-03Too long DHW heat-up time required