Bosch Compress A51-6022 fault code
Bosch Compress heat pumps
What the Bosch Compress A51-6022 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The bottom cylinder sensor has failed and heating has dropped to standby.
Source: Worcester Bosch user interface HPC 410 manual 6721832682 (2021/02) §8 Unit troubleshooting, Table 35
Likely causes
- Configuration requires a bottom cylinder sensor
- Broken connection to the solar module
- Loose screw or plug at the solar module
- Sensor out of tolerance
- Solar module fault
First check
Bosch check 1 of 5 — Check the configuration — the selected setting requires a bottom cylinder temperature sensor.
Source: Worcester Bosch user interface HPC 410 manual 6721832682 (2021/02) §8 Unit troubleshooting, Table 35
UK models this code applies to
Tap yours to open A51-6022 on that machine.
Now the harder half: proving what caused it
A51-6022 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase A51-6022 on your machine →Free, no sign-up. Pick the model: where we hold Bosch's own chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- A11-1000System configuration not confirmed
- A11-1010No communication via BUS interface EMS 2
- A11-1037Outside temperature sensor: heating standby mode active
- A11-1038Invalid time/date
- A11-3061…3064No communication with mixer module (3061 = heating circuit 1 … 3064 =…
- A11-3091…3094Room temperature sensor defective (3091 = heating circuit 1 … 3094 =…
- A11-6004No communication with solar module
- A31…A34-3021…3024Heating circuit 1…4 flow temperature sensor faulty: standby mode…
- A51-6021Solar collector temperature sensor defective
- A61…A64-1081…1084Two master control units in the system (A61/1081 = heating circuit 1…