Bosch Compress A11-1037 fault code
Bosch Compress heat pumps
What the Bosch Compress A11-1037 fault code means, from the manufacturer's own service literature, and the UK models it applies to.
What it means
The outside sensor is missing or out of tolerance, so heating has dropped to standby. A61…A64 are the same fault reported per heating circuit 1…4.
Source: Worcester Bosch user interface HPC 410 manual 6721832682 (2021/02) §8 Unit troubleshooting, Table 28
Likely causes
- Configuration requires an outside sensor that is not fitted
- Break in the sensor lead
- Corroded terminals in the outside sensor housing
- Sensor out of tolerance
- Control unit fault
First check
Bosch check 1 of 5 — Check the configuration — the selected setting requires an outside temperature sensor.
Source: Worcester Bosch user interface HPC 410 manual 6721832682 (2021/02) §8 Unit troubleshooting, Table 28
UK models this code applies to
Tap yours to open A11-1037 on that machine.
Now the harder half: proving what caused it
A11-1037 names a symptom, not a root cause. Pick your model and the wizard takes this code one question at a time. To prove the cause, the guided investigation asks what to measure and ends on an honest verdict — including “nothing in this machine is broken” when that's what the readings say.
Chase A11-1037 on your machine →Free, no sign-up. Pick the model: where we hold Bosch's own chart for it, it takes you through one question at a time.
Or watch one get chased — free demo →Prove the cause: guided investigation →The first steps are free to try, no account. Your first full investigation is free with one.
One full investigation is free with a free account.
Related codes
- A01-811DHW provision: thermal disinfection unsuccessful
- A01-5378Outdoor unit defrost failure
- A01-5522Wrong combination of indoor and outdoor units
- A11-1000System configuration not confirmed
- A11-1010No communication via BUS interface EMS 2
- A11-1038Invalid time/date
- A11-3061…3064No communication with mixer module (3061 = heating circuit 1 … 3064 =…
- A11-3091…3094Room temperature sensor defective (3091 = heating circuit 1 … 3094 =…
- A11-6004No communication with solar module
- A31…A34-3021…3024Heating circuit 1…4 flow temperature sensor faulty: standby mode…